Type |
Digital power meters |
Measuring Parameters |
Current (AC), Current demand (DA), Voltage (L-L), Voltage (L-N), Frequency (Hz), Apparent energy (VAh), Reactive energy (varh), Apparent power (VA), Reactive power (var), Power factor (PF), Harmonic current (HI), Harmonic voltage (HV), Rolling demand active power (DW), Rolling demand apparent power (DVA), Rolling demand reactive power (Dvar), Periodic active energy (Wh), Operating time (h), Current unbalance rate (Aunb), Voltage unbalance rate (Vunb), CO2 equivalent |
Rated power supply |
220VAC |
Measurement input type |
AC current, AC voltage |
Voltage measurement range |
220 V AC (DELTA), 440 V AC (STAR) max. (1-phase 2-wire), 440 V AC (STAR) max. (3-phase 3-wire), 222/440 V AC max. (1-phase 3-wire), 277/480 V AC max. (3-phase 4-wire) |
Current measurement range |
1...5A |
Display type |
LCD with LED backlight |
Number of digit |
3 rows with 4 digits per row, 1 row with 6 digits |
Display unit |
AAC, ADC, VAC, VDC, Hz, kVA, kVAR, kW, PF, kWh, kVArh |
PV character colour |
Black |
SV character colour |
Black |
Communication protocol |
Modbus RTU |
Feature |
High performance model, No bar graph, Standard model, Graph |
Mounting method |
Flush mounting |
Panel cutout |
W96xH96mm |
Connection method |
Screw terminal |
Ambient temperature |
-5...55°C |
Representative standard |
RoHS |
Approx. weight |
500g |
Overall width |
96mm |
Overall height |
96mm |
Overall depth |
90mm |
Option (Sold separately) |
ME-0000BU-SS96, ME-0000MT-SS96, ME-0040C-SS96, ME-0040MT2-SS96, ME-0052-SS96, ME-4210-SS96B |